Communicate with Supplier? Supplier
Ray Guo Mr. Ray Guo
What can I do for you?
Contact Supplier

TANDA

HomeProductsIntelligent Fire Alarm SystemAddressable Fire Alarm ModuleDouble Input-Double Output Module
  • Double Input-Double Output Module

Double Input-Double Output Module

    Payment Type: L/C,T/T,D/P
    Incoterm: FOB,CFR,CIF,EXW,FCA,CPT,CIP
    Min. Order: 1 Bag/Bags

Basic Info

Model No.: TX7220

Additional Info

Packaging: Carton

Brand: TNA

Transportation: Ocean,Air

Place of Origin: SHENZHEN

Port: YANTIAN,SHEKOU

Product Description

Addressable Dual Input/Output Module

The TX7220 Addressable Dual Input/output Module is characterized as two inputs or outputs volt free relay and control module. The unit is normally used for overriding equipment such as lift return, door holder, smoke extract fans, air handling unit, auto dialler to fire brigade, BMS and etc. The unit has built-in feedback signal feature, according to the pre-configured interface module command fire scenario, the alarm controller send out start command to the equipment required to start. After receiving the command, output module enables its relay to change state. Once the module is under control and operated a confirmation signal will be sending back to the alarm controller. In addition, the unit incorporates an intelligent processor that provides automatic monitoring for both open and short circuit of the input signal line.

The unit manufactured base on the requirement of EN 54 part 18, European Standard. The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs and its plug-in type assembles make installation and maintenance more convenient to the installer. The unit is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel, produced by single manufacture T&A, to avoid addressable communication compatibility problem.


Feature and Benefits
  • EN54-18 Compliance
  • Built-in MCU processor and digital addressing
  • Two circuits 24VDC/2A Output relay contact and Control module
  • Two circuits Input Fire or Supervisory signal configuration
  • Dis/Enable Input and output cable monitored
  • LED status indicator
  • Onsite Adjustable Parameter
  • Loop or external power input
  • Aesthetically pleasing design
  • Surface mounting with fix base for simple installation

Technical Specification

  • Listed LPCB Pending
  • Compliance EN54-18:2005
  • Input Voltage Loop Power:24VDC [16V to 28V]
External PSU: 20 to 28VDC
  • Current Consumption Loop: Standby 0.6mA, Alarm: 2.6mA
PSU: Standby 0.6mA, Alarm: 45mA
  • Control output voltage 24VDC / 2A rating (per circuit)
  • Input Relay Normally Open dry contact
  • Input Resistance 5.1Kohms/ ¼ W (per circuit)
  • Protocol/Addressing T&A, Value range from 1 to 254
  • Indicator Status Normal: Single blink/Active: Steady/Fault: Double Blink
  • Material / Colour ABS / White Glossy finishing
  • Dimension / LWH 108 mm x 86 mm x38 mm
  • Weight 182g (with Base), 100g (without Base)
  • Operating Temperature -10°C to +50°C
  • Ingress Protection Rating IP30
  • Humidity 0 to 95% Relative Humidity, Non condensing
Addressable Dual Input Output Module










Looking for ideal Double Input-Double Output Module GST Manufacturer & supplier ? We have a wide selection at great prices to help you get creative. All the GST Double Input-Double Output Module are quality guaranteed. We are China Origin Factory of Double Input-Double Output Module Honeywell. If you have any question, please feel free to contact us.